DC Scheduled Intrusive HV Maintenance – Global Switch - London

Scheduled for Mar 19, 07:00 - 22:00 UTC

Scheduled

Maintenance Window:
• Start Date: 19th March 2025 – 07:00 GMT
• End Date: 19th March 2025 – 22:00 GMT
• Duration: 1 Day

Location & Affected Areas:
• Site: Global Switch – London East
• Impacted Areas: LONE: 4 & 5, LONN: A03, A04, B07, C03 & C09

Scope of Work:

This is a scheduled critical maintenance activity involving PowerStation ‘B’ BA/IT Board RHS. The activity includes:
• Pre- and post-maintenance functional checks
• Protection testing
• Busbar inspections
• Isolation of BA/IT Board RHS 11kV Bus section
• System validation and reinstatement procedures

This maintenance is part of a 5-year intrusive maintenance program.

Impact & Risk Assessment:
• Medium Risk Level: The maintenance will result in a temporary reduction in resilience while maintaining an N+2 backup system.
• The system operates on a Closed Ring topology, and during maintenance, an Open Ring configuration will be in place to ensure continuous service.
• No expected impact on ‘B’ supply areas.

If you have any concerns during this maintenance period, please contact Taiga Cloud Customer Support via the ticket portal or cloud-support@taigacloud.com

Thank you for your patience and understanding as we work to maintain a resilient and reliable infrastructure.
Posted Feb 17, 2025 - 10:52 UTC
This scheduled maintenance affects: Taiga Cloud Network (Availability United Kingdom (cluster ndcloud-njoerd)).